Pump head is the energy the pump adds to the water, expressed as a height of water in metres. It is one of the two numbers, with flow, that define a pump selection. Get the head wrong and the pump either cannot deliver water where it is needed or wastes energy.
Why head is measured in metres
Head expresses pressure as the height of a water column. 10 m of head is about 1 bar of pressure for water. Using metres makes pump curves independent of the liquid’s density and easy to relate to building heights.
Conversions:
- 1 bar is about 10.2 m of water
- 1 m of water is about 0.098 bar
- 1 psi is about 0.70 m of water
The components of total head
Total head = static head + friction head + residual (pressure) head + velocity head
1. Static head
The vertical distance the water is lifted, from the water level on the suction side to the highest discharge point.
- If the pump draws from a tank above it (flooded suction), static head is the height from the tank water level to the discharge point. The water above the pump helps.
- If the pump draws from a tank below it (suction lift), static head is from the lowest water level to the discharge point.
Use the lowest expected water level in the suction tank, not the full level.
2. Friction head
Water loses energy as it flows through pipes and fittings. Friction losses depend on flow, pipe diameter, pipe length, pipe material and the number of fittings.
Calculate pipe losses using friction loss tables or the Hazen-Williams or Darcy-Weisbach equations. Add fitting losses using equivalent lengths or K-factors for elbows, tees, valves, strainers, meters and non-return valves.
Calculate along the index circuit: the route to the outlet with the highest combined height and friction.
3. Residual pressure head
The pressure required at the outlet or equipment at the end of the line. For example:
- A shower may need 1 to 2 bar (10 to 20 m)
- A flush valve may need more
- Equipment such as a water heater or RO unit has its own minimum inlet pressure
If the pump discharges into an open tank, residual pressure is near zero.
4. Velocity head
The energy in moving water, v²/2g. In building systems with normal pipe velocities it is small, often under 0.2 m, and is usually included in the friction allowance.
Worked example
A transfer pump fills a roof tank from an underground tank.
- Lowest water level in the underground tank: 3 m below ground
- Roof tank inlet: 45 m above ground
- Static head: 3 + 45 = 48 m
- Pipe: 60 m of 50 mm pipe at 3 l/s. Friction from tables: about 3.5 m per 100 m, so 2.1 m
- Fittings: 8 elbows, 2 gate valves, 1 non-return valve, 1 strainer, adding about 2.5 m
- Friction head: 2.1 + 2.5 = 4.6 m
- Residual at the float valve inlet: 3 m
- Total head: 48 + 4.6 + 3 = about 56 m
Select a pump delivering 3 l/s (10.8 m³/h) at 56 m. A small allowance for pipe ageing is reasonable; large margins lead to oversizing.
Checking suction conditions
When a pump lifts from below, check that the net positive suction head available (NPSHa) is greater than the pump’s NPSH required, with a margin. Otherwise the pump will cavitate. See what is NPSH.
Common mistakes
- Using the full tank level instead of the lowest level
- Leaving out losses through strainers, meters and valves
- Calculating friction on the shortest route instead of the index circuit
- Adding a large safety margin on top of every component
Frequently asked questions
Is head the same as pressure?
They describe the same thing in different units. Head is in metres of liquid; pressure is in bar or psi.
Does pipe diameter affect head?
Yes. Smaller pipes have higher friction losses at the same flow, increasing the head the pump must produce.
What if my calculation gives a head between two pump models?
Choose the pump that meets the duty closest to its best efficiency point. A VFD can fine-tune the duty after commissioning.
Next step
For complex buildings, Lifeline can carry out the calculation for you. See our hydraulic calculations resources or contact Lifeline.