Flow rate is the volume of water a pump must deliver in a given time. It is the first number in any pump selection. The method depends on what the pump does, so this guide covers the four most common cases in buildings.

Units and conversions

  • 1 litre per second (l/s) = 3.6 m³/h = 60 litres per minute
  • 1 m³/h = 16.67 litres per minute
  • 1 US gallon per minute (GPM) = 0.227 m³/h
  • 1 imperial gallon = 4.546 litres

Case 1: Domestic water supply (booster pumps)

For pumps that supply outlets, flow is based on probable peak demand, not the total of every outlet.

  1. List the fixtures served.
  2. Assign each a loading unit or fixture unit from the design code.
  3. Sum the units.
  4. Convert the total to a design flow using the code’s table or curve.

Add any continuous demands, such as process or irrigation water, on top.

Example: A residential floor plate’s fixture units convert to 1.2 l/s. Five floors served by the same booster set give a combined total of units that converts to about 3 l/s. The flow does not increase in proportion to the number of floors, because the probability of simultaneous use falls.

Case 2: Filling a tank (transfer pumps)

Flow is the volume to be delivered divided by the time allowed.

Flow = volume ÷ time

Example: A 30 m³ roof tank should refill in 2 hours while the building uses water at an average of 5 m³/h.
Flow = 30 ÷ 2 + 5 = 20 m³/h.

Also check the number of starts per hour. The volume between the pump’s start and stop levels should prevent the pump starting more often than the motor allows.

Case 3: Heating and cooling (circulation pumps)

Flow is set by the heat load and the temperature difference across the system.

Flow (l/s) = load (kW) ÷ (4.19 × ΔT)

where 4.19 is the specific heat of water in kJ/kg°C and ΔT is the temperature difference in °C.

Example: A chilled water circuit serving 350 kW with a 5.5°C ΔT.
Flow = 350 ÷ (4.19 × 5.5) = about 15.2 l/s, or 54.7 m³/h.

For tons of refrigeration: 1 TR = 3.517 kW.

Case 4: Irrigation

Flow per zone is the number of emitters or sprinklers multiplied by the flow of each.

Example: A zone with 400 drippers at 4 litres per hour = 1,600 l/h = 1.6 m³/h. If three zones run at once, the pump must deliver 4.8 m³/h at the required pressure.

Measuring flow on an existing system

  • Read a flow meter if one is installed
  • Time how long it takes to fill a known volume, such as a tank or bucket
  • Use the pump curve: measure the pressure on the suction and discharge, calculate the head, and read the flow from the curve (an estimate only)
  • Use a clamp-on ultrasonic flow meter for an accurate reading without cutting pipes

Common mistakes

  • Adding the full flow of every outlet, which greatly oversizes domestic pumps
  • Forgetting simultaneous demands from other services
  • Using the wrong ΔT in HVAC calculations
  • Mixing units, especially US and imperial gallons

Frequently asked questions

Does flow rate change with pipe size?

The flow a system needs does not change, but pipe size affects friction, which affects the head the pump must produce to deliver that flow.

What happens if the pump flow is too high?

The pump runs to the right of its best efficiency point, uses more energy and may cavitate or vibrate. In closed loops it can cause noise and erosion.

Can Lifeline calculate the flow for us?

Yes. Send your drawings and fixture schedules.

Next step

Once you have flow, calculate head. See how to calculate pump head for a building, or contact Lifeline for a full calculation.