NPSH stands for Net Positive Suction Head. It describes the pressure conditions at the inlet of a pump. If the pressure at the inlet is too low, water starts to boil inside the pump even at normal temperature, and the pump cavitates. Checking NPSH is how engineers make sure that does not happen.

The two NPSH values

NPSH available (NPSHa) is a property of your installation. It is the pressure head at the pump suction above the vapour pressure of the water. It depends on the tank level, the height of the pump, suction pipe losses and water temperature.

NPSH required (NPSHr) is a property of the pump. The manufacturer publishes it on the pump curve. It is the minimum suction head the pump needs at each flow to avoid significant cavitation. NPSHr rises as flow increases.

The rule: NPSHa must be greater than NPSHr across the operating range, with a safety margin. A margin of at least 0.5 to 1 m, or 10 to 30% depending on the application, is common practice.

Calculating NPSH available

NPSHa = Ha ± Hz – Hf – Hvp

where:

  • Ha = atmospheric pressure head on the water surface, about 10.3 m at sea level for an open tank
  • Hz = static height of the water level above the pump centreline (positive) or below it (negative)
  • Hf = friction losses in the suction pipe, fittings, valves and strainer
  • Hvp = vapour pressure head of the water at its temperature

Why temperature matters in the UAE

Vapour pressure rises sharply with temperature:

Water temperatureVapour pressure head (approx.)
20°C0.24 m
40°C0.75 m
60°C2.0 m
80°C4.8 m

Rooftop tanks in a UAE summer can reach 40 to 45°C, and hot water systems run at 60°C or more. Hot water reduces NPSHa, so pumps on hot water service need more careful suction design.

Worked example

A transfer pump lifts water from an underground tank. The lowest water level is 3 m below the pump centreline. Water temperature is 35°C. Suction pipe losses at duty flow are 0.8 m.

  • Ha = 10.3 m
  • Hz = -3 m
  • Hf = 0.8 m
  • Hvp at 35°C = about 0.57 m

NPSHa = 10.3 – 3 – 0.8 – 0.57 = 5.9 m

If the pump curve shows NPSHr of 3.5 m at duty flow, the margin is 2.4 m, which is acceptable. If NPSHr were 5.5 m, the margin would be too small and the pump would be at risk of cavitation, especially at higher flows.

How to improve NPSH available

  • Install the pump with flooded suction, below the tank’s lowest water level
  • Shorten the suction pipe and increase its diameter
  • Remove unnecessary bends and fittings on the suction side
  • Keep suction strainers clean
  • Use eccentric reducers with the flat side on top to avoid air pockets
  • Avoid running the pump far to the right of its curve, where NPSHr is high

Signs of NPSH problems

  • A rattling noise like gravel in the pump
  • Vibration and fluctuating discharge pressure
  • Reduced flow and head
  • Pitting damage on the impeller

See pump cavitation: causes, signs and prevention.

Frequently asked questions

Is NPSHr the same for every flow?

No. NPSHr increases as flow increases. Check it at the highest flow the pump will see.

Does a booster pump with flooded suction need an NPSH check?

It is less likely to be a problem, but still check, especially for hot water and at low tank levels.

What is NPSH3?

Manufacturers often publish NPSHr as NPSH3: the suction head at which the pump’s head drops by 3% due to cavitation. Some cavitation already occurs at this point, which is why a margin is needed.

Next step

See our product selection guidance, or send your suction arrangement and duty to Lifeline for a checked selection.